Armstrong Suction Guides
- Applications-HVAC-system pumping; general purpose pumping; industrial/process pumping (water or glycol based).
- Description-The Armstrong Suction Guides (SG) are multi-function pump fittings that provide a 90° elbow, guide vanes, and an in-line strainer. Suction guides reduce pump installation cost and floor space requirements.
- Materials (MOC)-Cast Iron, ductile iron; grooved, flanged or threaded connections
- Performance range-Suitable for all Armstrong commercial pumps and pumping systems
- Temperature-230°F (110°C)
- Size-1.5” to 20” (40 mm to 500 mm)
Description
Benefits & Features
Reduced installation cost and footprint
- No separate in-line strainers, long-radius elbows and superfluous piping. (less material cost)
- Fewer pipe connections, down from five (or more) to two (less labor cost)
- Reduced floor space requirements of up to 20% compared to traditional piping.
- Use of Flow-Trex valves yields further space savings.
Related products
Armstrong 4380 vertical in-line pumps
- Applications-HVAC-system pumping; light industrial/ process pumping. (water or glycol based)
- Description-The Armstrong 4380 pipe-mounted pumps are designed for space-saving installation and long service life.
- Materials(MOC)-Cast iron or ductile iron casing, Silicon sintered carbide mechanical seal, Cast iron or bronze impeller.
- Configuration-Inside single-spring mechanical seal.
- Performance range-Up to 2,500 USgpm (160 L/s) flow; up to 300 ft (90 m) head
- Temperature-250°F (121°C)
- Power Range-0.33 hp to 60 hp (0.25 kW to 45 kW)
- Size-1.5″ to 8″ (40 mm to 200 mm)
Armstrong Design Envelope 4302 Dualarm Pumps
- Applications-HVAC system pumping; general purpose pumping; industrial/process pumping (water or glycol based) Armstrong Design Envelope Pumps with integrated controllers are OSHPD pre-approved!
- Description-Pipe-mounted 2-pump unit with integrated intelligent controls for space-saving installation, superior energy performance, and full redundancy or parallel-pumping operation. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations.
- Materials (MOC)-Cast iron or ductile iron casing, Cast iron or bronze impeller, Sintered silicon carbide mechanical seal
- Configuration-On-board Intelligent Variable Speed controls with Sensorless or Parallel Sensorless control. Controls enclosure UL type 12 or UL type 4X (outdoor applications). Available with NEMA premium motors. Outside balanced or inside single spring mechanical seal
- Performance range-Up to 1250 USgpm flow and 250 ft head (80 L/s, 76 m)
- Temperature-250°F (121°C)
- Power Range-0.33 hp to 75 hp (0.25 kW to 55 kW)
- Size –1″ to 8” (25 mm to 200 mm)
Armstrong Design Envelope Compass h Circulators
- Applications-Residential heating and cooling; potable water supply.
- Description-The Armstrong Compass H is an energy-efficient variable speed wet-rotor circulator. Designed to replace existing fixed speed circulators, with popular flange-to-flange dimensions, Compass H can be considered a universal replacement for all circulators in its capacity range.
- Materials (MOC)-Cast iron and stainless steel volutes.
- Configuration-Eight operation modes with patented “Auto” algorithm, four Sensorless modes and three fixed speed modes. 50 Hz and 60 Hz designs
- Performance range-Up to 20 USgpm (1.26 L/s) flow; up to 20 ft (6.1 m) head
- Temperature-Max ambient temp. 40°C; max water temp. 110°C
- Power Range-5 W to 45 W
- Size-1″
Armstrong Design Envelope Integrated Pumping System (IPS 4000)
- Applications-Multi-pump control for heated – or chilled – water system optimization in buildings.
- Description-The Design Envelope Integrated Pumping System (IPS 4000) is an advanced multi-zone control that directly integrates with pumping units to optimize energy performance, system handling, and installation.
- Materials (MOC)-Enclosure, circuitry, software
- Configuration-Integrates seamlessly with Armstrong Design Envelope pumps in a headered configuration.
- Performance range-Up to 8 pumps, 16 zones (variable primary, secondary or tertiary) and 8 flow sensitive equipment (variable primary) IPS 4001w / IPS 4501w for up to 3 pumps, 3 zones and 3 flow sensitive equipment IPS 4002w / IPS 4502w for up to 4 pumps, 6 zones and 4 flow sensitive equipment IPS 4003w / IPS 4503w for up to 6 pumps, 12 zones and 6 flow sensitive equipment IPS 4004w / IPS 4504w for up to 8 pumps, 16 zones and 8 flow sensitive equipment
- Power Range-No limitations in system size and capacity.
- Size-No limitations in system size.
Armstrong Firepak Vertical In-line
- Applications-Fire-protection of buildings and other built infrastructure.
- Description-The Armstrong Vertical In-line (VIL) FirePak line features the full range of VIL fire pumps with electric motor and controller. All mounted, piped, and wired on a base at the factory. The complete package is designed to fit through a standard door.
- Materials (MOC)-Metal base, piping, pump, and control panel; switchgear; electric motor.
- Configuration-Options available include jockey pump and jockey pump controller. 50 Hz and 60 Hz designs. UL, ULC, and/or FM certification
- Performance range-50 – 1500 USgpm
Full View Sight Glass (PN10)
Applications:
Industrial facilities, oil refineries, bath soap manufacturing plane, gas industries, petrochemical complex, high viscous process media, building construction, environmental water treatments, synthetics, plastic and resin industries, polymer manufacturing plant, food industries (chocolate, sauce etc.), fertilizer industries etc.Technical Data :
| Design Std. | As per BS 5352 |
| Testing Std. | As per API 598 |
| End Connection | As per ANSI B16.5 |
| Size | ½” to 4” (15 mm to100 mm) |
| Pressure rating | PN10 |
| Maximum working pressure | 10 Kg/cm2 |
| Test pressure | 15 Kg/cm2 |
Dimensions
| Size | A | B | C |
| 15 | 153 | 51 | 137 |
| 20 | 153 | 51 | 137 |
| 25 | 153 | 51 | 137 |
| 40 | 178 | 64 | 146 |
| 50 | 190 | 76 | 190 |
| 75 | 229 | 102 | 132 |
| 100 | 299 | 127 | 283 |
All dimensions are in mm.
POT-BASKET TYPE STRAINER (ANSI 150#, 300#)
Applications:
Strainer can be used in liquid as well as gas line, Regulator and valve protection, steam traps protections, flow meter and pump protections, heat exchanger and refrigeration set protection, Suitable for Hazardous environments. Y-Strainers and pot basket type strainers is a device for mechanically removing unwanted solids from liquid, gas or steam lines by means of a perforated or wire mesh straining element. Where the amount of material to be removed from the flow is relatively small, resulting in long intervals between screen cleanings, the strainer screen is manually cleaned by shutting down the line and removing the strainer cap.Technical Data :
| Design Std. | As per ASME B16.34 |
| Testing Std. | As per API 598 |
| End Connection | Flanged Drill as per ANSI B16.5 |
| Material | Body : IS 2062, Seal : NBR / PTFE / Graphite + SS, Mesh : SS |
| Shell Wall Thickness | As per ANSI B16.34 |
| Size | 2" to 18", Class 150, 300 |
Dimensions 150#
| Size | F/F | A | B |
| 50 | 320 | 190 | 285 |
| 80 | 360 | 200 | 320 |
| 100 | 400 | 210 | 360 |
| 125 | 460 | 230 | 430 |
| 150 | 510 | 240 | 430 |
| 200 | 560 | 280 | 530 |
| 250 | 810 | 420 | 635 |
| 300 | 890 | 430 | 715 |
Dimensions 300#
| Size | F/F | A | B |
| 50 | 380 | 200 | 305 |
| 80 | 420 | 235 | 400 |
| 100 | 475 | 260 | 405 |
| 125 | 510 | 275 | 435 |
| 150 | 620 | 295 | 490 |
| 200 | 630 | 345 | 560 |
| 250 | 900 | 390 | 690 |
| 300 | 1000 | 440 | 770 |
All dimensions are in mm.
Y-Type Strainers (ANSI 150#, 300#)
Applications:
Strainer can be used in liquid as well as gas line, Regulator and valve protection, steam traps protections, flow meter and pump protections, heat exchanger and refrigeration set protection, Suitable for Hazardous environments. Y-Strainers and pot basket type strainers is a device for mechanically removing unwanted solids from liquid, gas or steam lines by means of a perforated or wire mesh straining element. Where the amount of material to be removed from the flow is relatively small, resulting in long intervals between screen cleanings, the strainer screen is manually cleaned by shutting down the line and removing the strainer capTechnical Data :
| Design Std. | As per ASME B16.34 |
| Testing Std. | As per API 598 |
| End Connection | Flanged End as per ANSI B16.5, F to F as per ANSI B16.10 |
| Shell Wall Thickness | As per ANSI B16.34 |
| Size 150# & 300# | 50 mm to 300 mm (2” to 12”) |
| Standard Trims | WCB / CF8M, Mesh : SS |
Dimensions 150#
| Size | ~L | ~H |
| 50 | 225 | 190 |
| 80 | 315 | 270 |
| 100 | 370 | 305 |
| 150 | 470 | 400 |
| 200 | 600 | 490 |
| 250 | 695 | 670 |
| 300 | 810 | 800 |
Dimensions 300#
| Size | ~L | ~H |
| 50 | 270 | 190 |
| 80 | 320 | 270 |
| 100 | 355 | 305 |
| 150 | 450 | 400 |
| 200 | 560 | 490 |
| 250 | 730 | 670 |
| 300 | 850 | 800 |
All dimensions are in mm.