Armstrong Design Envelope 4302 Dualarm Pumps
- Applications-HVAC system pumping; general purpose pumping; industrial/process pumping (water or glycol based)
Armstrong Design Envelope Pumps with integrated controllers are OSHPD pre-approved! - Description-Pipe-mounted 2-pump unit with integrated intelligent controls for space-saving installation, superior energy performance, and full redundancy or parallel-pumping operation. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations.
- Materials (MOC)-Cast iron or ductile iron casing, Cast iron or bronze impeller, Sintered silicon carbide mechanical seal
- Configuration-On-board Intelligent Variable Speed controls with Sensorless or Parallel Sensorless control. Controls enclosure UL type 12 or UL type 4X (outdoor applications). Available with NEMA premium motors. Outside balanced or inside single spring mechanical seal
- Performance range-Up to 1250 USgpm flow and 250 ft head (80 L/s, 76 m)
- Temperature-250°F (121°C)
- Power Range-0.33 hp to 75 hp (0.25 kW to 55 kW)
- Size –1″ to 8” (25 mm to 200 mm)
Description
Benefits & Features
Lowest installed cost
- Vertical In-line design eliminates the need inertia bases, housekeeping pads, and flex connectors and reduces piping requirements.
- 2-pump casing for reduced footprint.
- Integrated, intelligent controls eliminate the need for procurement, installation (incl. wiring), calibration and upkeep of differential pressure sensor.
- Superior energy performance qualifies for significant cost recovery under utility and government rebate programs.
- Design Envelope selections frequently recommend a smaller motor and/or pump which reduces installed cost.
Lowest operating cost
- Integrated intelligent controls – combined with perfect component match-up and tuning – for up to 75% in energy savings over traditional constant speed and variable frequency operated pumping installations.
- Available with Parallel Sensorless control (patent pending) to provide best-efficiency staging of both pumps for additional energy savings.
- Shorter pipe runs reduce system friction
Lowest energy consumption and carbon emissions
- Integrated intelligent controls – combined with perfect component match-up and tuning – for up to 75% lower energy consumption and carbon (greenhouse gas) emissions.
- Available with Parallel Sensorless control (patent pending) for best-efficiency staging of both pumps leading to additional energy savings.
Lowest project and operating risk
- Integrated intelligent controls – combined with perfect component match-up and tuning – for fast and easy commissioning.
- Integrated intelligent controls for reduced radio frequency interference/ improved electromagnetic compatibility.
- Single source-responsibility for optimum design and field support.
- DualArm pumps are designed for full redundancy in case of emergency or routine servicing (each pump can be individually isolated from the system with the second pump still operating)
- ETL Listed – conforms to UL STD 778
- Certified to CSA STD C22.2 NO.108
- OSHPD Special Seismic Certification Pre-approval (OSP) No OSP-0422-10
Related products
Armstrong 4030 End Suctionbase Mounted Pumps
- Applications — HVAC-system pumping; light industrial/ process pumping
- Description — The Armstrong 4030 horizontal end-suction (ES) pumps are engineered to substantially reduce cost over competitor designs across installation, operation, and lifetime maintenance. High-efficiency NEMA-premium motors ensure low energy consumption and cost.
- Materials (MOC) — Cast iron, ductile iron, or bronze casing, Cast iron or bronze impeller
- Configuration Inside — single spring mechanical seal.
- Performance range — Up to 5,000 USgpm (315 L/s) flow; up to 600 ft (180 m) head
- Temperature — 250°F (121°C)
- Power Range — 0.33 hp to 300 hp (0.25 kW to 200 kW)
- Size — 1" to 8” (25 mm to 200 mm)
Armstrong 4300 vertical in-line pumps
- Applications-HVAC-system pumping; light industrial/ process pumping (water or glycol based)
- Description-The Armstrong 4300 pipe-mounted pumps are designed for space-saving installation, high operating efficiency, and long service life
- Materials(MOC)-Cast, ductile iron or bronze casing, Cast iron or bronze impeller
- Configuration-Outside balanced or inside single spring mechanical seal
- Performance range-Up to 28,000 USgpm (1,800 L/s) Flow; up to 500 ft (150 m) Head
- Temperature-300oF (150oC)
- Power Range-1 hp to 1250 hp (0.75 kW to 900 kW)
- Size-1.5″ to 20” (40 mm to 500 mm)
Armstrong Design Envelope 4300 Pumps
- Applications-HVAC-system pumping and control; general purpose pumping; industrial/process pumping and control. (water or glycol based)
- Description-Pipe-mounted UL 778 pumping unit with integrated intelligent controls for space-saving installation and superior energy performance. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations. Remote services through internet to enhance reliability and sustain optimal performance over life of pumps.
- Materials(MOC)-Ductile iron e-coated casing, Stainless steel impeller, Sintered silicon carbide mechanical seal
- Configuration-On-board Intelligent Variable Speed controls with Sensorless control. Split-coupling design and outside balanced or inside single spring mechanical seal. Controls enclosure UL type 12 or UL type 4X for outdoor applications. 0.33-50hp range standard with DEPM motors that reduce losses by more than 20% over NEMA Premium efficiency. Network capable for remote performance management services.
- Performance range-25 to 25,000 USgpm (1.5 to 1500 L/s) flow; 10 to 300 ft (3 to 90 m) head (composite curves available)
- Temperature-300oF (150oC)
- Power Range-0.33 hp to 1250 hp (0.25 kW to 900 kW)
- Size-1″ to 20″ (25 mm to 500 mm)
Armstrong Design Envelope Chilled-Water Integrated Plant Package
- Applications-Commercial and industrial chilled-water cooling systems.
- Description-The Armstrong Chilled-Water Integrated Plant Package combines all the equipment needed to deliver chilled water to medium to large size buildings at superior energy efficiency. The factory-assembled plant includes pumps, integrated controls, water-cooled chillers and the requisite instrumentation, valves and sensors. IPP complies with all ASHRAE 189.1 requirements and exceeds ASHRAE 90.1.
- Configuration-Variable primary with variable condenser flow. Catalogue-based pre-engineered solutions or designed to customer specification. BMS communications protocol available
Armstrong Design Envelope Compass h Circulators
- Applications-Residential heating and cooling; potable water supply.
- Description-The Armstrong Compass H is an energy-efficient variable speed wet-rotor circulator. Designed to replace existing fixed speed circulators, with popular flange-to-flange dimensions, Compass H can be considered a universal replacement for all circulators in its capacity range.
- Materials (MOC)-Cast iron and stainless steel volutes.
- Configuration-Eight operation modes with patented “Auto” algorithm, four Sensorless modes and three fixed speed modes. 50 Hz and 60 Hz designs
- Performance range-Up to 20 USgpm (1.26 L/s) flow; up to 20 ft (6.1 m) head
- Temperature-Max ambient temp. 40°C; max water temp. 110°C
- Power Range-5 W to 45 W
- Size-1″
Armstrong Design Envelope Integrated Pumping System (IPS 4000)
- Applications-Multi-pump control for heated – or chilled – water system optimization in buildings.
- Description-The Design Envelope Integrated Pumping System (IPS 4000) is an advanced multi-zone control that directly integrates with pumping units to optimize energy performance, system handling, and installation.
- Materials (MOC)-Enclosure, circuitry, software
- Configuration-Integrates seamlessly with Armstrong Design Envelope pumps in a headered configuration.
- Performance range-Up to 8 pumps, 16 zones (variable primary, secondary or tertiary) and 8 flow sensitive equipment (variable primary)
IPS 4001w / IPS 4501w for up to 3 pumps, 3 zones and 3 flow sensitive equipment
IPS 4002w / IPS 4502w for up to 4 pumps, 6 zones and 4 flow sensitive equipment
IPS 4003w / IPS 4503w for up to 6 pumps, 12 zones and 6 flow sensitive equipment
IPS 4004w / IPS 4504w for up to 8 pumps, 16 zones and 8 flow sensitive equipment - Power Range-No limitations in system size and capacity.
- Size-No limitations in system size.
Armstrong Firepak Vertical In-line
- Applications-Fire-protection of buildings and other built infrastructure.
- Description-The Armstrong Vertical In-line (VIL) FirePak line features the full range of VIL fire pumps with electric motor and controller. All mounted, piped, and wired on a base at the factory. The complete package is designed to fit through a standard door.
- Materials (MOC)-Metal base, piping, pump, and control panel; switchgear; electric motor.
- Configuration-Options available include jockey pump and jockey pump controller. 50 Hz and 60 Hz designs. UL, ULC, and/or FM certification
- Performance range-50 – 1500 USgpm
Armstrong Suction Guides
- Applications-HVAC-system pumping; general purpose pumping; industrial/process pumping (water or glycol based).
- Description-The Armstrong Suction Guides (SG) are multi-function pump fittings that provide a 90° elbow, guide vanes, and an in-line strainer. Suction guides reduce pump installation cost and floor space requirements.
- Materials (MOC)-Cast Iron, ductile iron; grooved, flanged or threaded connections
- Performance range-Suitable for all Armstrong commercial pumps and pumping systems
- Temperature-230°F (110°C)
- Size-1.5” to 20” (40 mm to 500 mm)

