Armstrong Suction Guides
- Applications-HVAC-system pumping; general purpose pumping; industrial/process pumping (water or glycol based).
- Description-The Armstrong Suction Guides (SG) are multi-function pump fittings that provide a 90° elbow, guide vanes, and an in-line strainer. Suction guides reduce pump installation cost and floor space requirements.
- Materials (MOC)-Cast Iron, ductile iron; grooved, flanged or threaded connections
- Performance range-Suitable for all Armstrong commercial pumps and pumping systems
- Temperature-230°F (110°C)
- Size-1.5” to 20” (40 mm to 500 mm)
Description
Benefits & Features
Reduced installation cost and footprint
- No separate in-line strainers, long-radius elbows and superfluous piping. (less material cost)
- Fewer pipe connections, down from five (or more) to two (less labor cost)
- Reduced floor space requirements of up to 20% compared to traditional piping.
- Use of Flow-Trex valves yields further space savings.
Related products
Armstrong 4030 End Suctionbase Mounted Pumps
- Applications — HVAC-system pumping; light industrial/ process pumping
- Description — The Armstrong 4030 horizontal end-suction (ES) pumps are engineered to substantially reduce cost over competitor designs across installation, operation, and lifetime maintenance. High-efficiency NEMA-premium motors ensure low energy consumption and cost.
- Materials (MOC) — Cast iron, ductile iron, or bronze casing, Cast iron or bronze impeller
- Configuration Inside — single spring mechanical seal.
- Performance range — Up to 5,000 USgpm (315 L/s) flow; up to 600 ft (180 m) head
- Temperature — 250°F (121°C)
- Power Range — 0.33 hp to 300 hp (0.25 kW to 200 kW)
- Size — 1" to 8” (25 mm to 200 mm)
Armstrong 4280 Motor Mounted Pumps
- Applications-HVAC-system pumping; light industrial / process pumping.
- Description-The Armstrong 4280 horizontal end-suction pumps are equipped with close-coupled motors to minimize footprint requirements.
- Materials(MOC)-Cast iron, ductile iron, or bronze casing, Cast iron or bronze impeller.
- Configuration-Inside single-spring mechanical seal
- Performance range-Up to 2,000 USgpm (125 L/s) flow; up to 400 f (120 m)
- Temperature-250°F (121°C)
- Power Range-0.33 hp to 60 hp (0.25 kW to 45 kW)
- Size-1" to 6” (25 mm to 150 mm)
Armstrong Air & Dirt Separators
- Applications-Dirt and air removal from hydronic and HVAC systems.
- Description-The Armstrong dirt & air separators (DAS) are designed to eliminate trapped air and suspended dirt particles associated with the start-up and maintenance of hydronic and HVAC systems.
- Materials (MOC)-Carbon steel (shell), stainless steel (coalescing medium), styrene butadiene rubber (gasket)
Armstrong Design Envelope 4302 Dualarm Pumps
- Applications-HVAC system pumping; general purpose pumping; industrial/process pumping (water or glycol based)
Armstrong Design Envelope Pumps with integrated controllers are OSHPD pre-approved! - Description-Pipe-mounted 2-pump unit with integrated intelligent controls for space-saving installation, superior energy performance, and full redundancy or parallel-pumping operation. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations.
- Materials (MOC)-Cast iron or ductile iron casing, Cast iron or bronze impeller, Sintered silicon carbide mechanical seal
- Configuration-On-board Intelligent Variable Speed controls with Sensorless or Parallel Sensorless control. Controls enclosure UL type 12 or UL type 4X (outdoor applications). Available with NEMA premium motors. Outside balanced or inside single spring mechanical seal
- Performance range-Up to 1250 USgpm flow and 250 ft head (80 L/s, 76 m)
- Temperature-250°F (121°C)
- Power Range-0.33 hp to 75 hp (0.25 kW to 55 kW)
- Size –1″ to 8” (25 mm to 200 mm)
Armstrong Design Envelope 9521 Integrated Plant Control System (IPC 9521)
- Applications-Automated chiller plant control for optimizing variable primary flow water-cooled chiller plants. The 9521 IPC works in a variable primary configuration and keeps the entire plant including water-cooled chillers, cooling towers, chilled water and condenser pumps running smoothly.
- Description-The Armstrong Integrated Water-Cooled Chiller Plant Control System (IPC) boosts energy efficiencies of new and existing chiller plant installations to leading class levels. The IPC 9521 works with all variable primary configurations, keeping the entire plant – including water-cooled chillers, cooling towers, chilled water and condenser pumps – running at optimum performance and occupant comfort.
- Configuration-Integrates with all brands of chillers, pumps, and automation systems. Installs directly with chiller plant equipment. If preferred, the IPC connects seamlessly with any central building automation system (BAS) maintaining full control of the chilled water plant through the BAS
- Performance range-Controls up to five chillers, five cooling towers and five pumps. No limitations in plant size and cooling capacity.
- Power Range-No limitations in plant cooling capacity
Armstrong Design Envelope Compass h Circulators
- Applications-Residential heating and cooling; potable water supply.
- Description-The Armstrong Compass H is an energy-efficient variable speed wet-rotor circulator. Designed to replace existing fixed speed circulators, with popular flange-to-flange dimensions, Compass H can be considered a universal replacement for all circulators in its capacity range.
- Materials (MOC)-Cast iron and stainless steel volutes.
- Configuration-Eight operation modes with patented “Auto” algorithm, four Sensorless modes and three fixed speed modes. 50 Hz and 60 Hz designs
- Performance range-Up to 20 USgpm (1.26 L/s) flow; up to 20 ft (6.1 m) head
- Temperature-Max ambient temp. 40°C; max water temp. 110°C
- Power Range-5 W to 45 W
- Size-1″
Armstrong Design Envelope Intelligent Fluid Management System
- Applications-Commercial or industrial closed-loop systems, including HVAC chilled-water systems, boiler systems, cooling tower systems, or process water loops.
- Description-The Armstrong Intelligent Fluid Management System (iFMS) integrates superior pump- and control technology into a single pumping solution yielding both compact and carefree installation as well as superior energy performance. iFMS is ideally suited for partial or all variable speed chilled-water plant applications (variable primary flow, variable secondary flow, variable condenser water flow). In combination with Parallel Sensorless control iFMS saves 30% or more in energy over any other parallel pumping configuration available today.
- Configuration-Up to 4 pumps in one unit. Catalogue-based pre-engineered solutions or designed to customer specification. Integrated control system (IPS 4000, IPC 11550) or connecting to chiller plant/BMS control. Optional single point power panel
Double Window Sight Glass (PN10, PN16)
Applications:
Industrial facilities, oil refineries, bath soap manufacturing plane, gas industries, petrochemical complex, high viscous process media, building construction, environmental water treatments, synthetics, plastic and resin industries, polymer manufacturing plant, food industries (chocolate, sauce etc.), fertilizer industries etc.
Technical Data :
| Design Std. | As per BS 5352 |
| Testing Std. | As per API 598 |
| End Connection | As per ANSI B16.5 |
| Size | 1/2” to 6” (15 mm to150 mm) |
| Size | 2" to 18", Class 150, 300 |
| Pressure rating | PN10 / PN16 |
| Maximum working pressure | 10 Kg/cm2 |
| Test pressure | 20 Kg/cm2 |
Dimensions
| Size | A | B | C |
| 15 | 153 | 51 | 137 |
| 20 | 153 | 51 | 137 |
| 25 | 153 | 51 | 137 |
| 40 | 178 | 64 | 146 |
| 50 | 190 | 76 | 190 |
| 75 | 229 | 102 | 232 |
| 100 | 299 | 127 | 283 |
| 150 | 406 | 191 | 368 |
All dimensions are in mm.