Armstrong Design Envelope 4300 Pumps
- Applications-HVAC-system pumping and control; general purpose pumping; industrial/process pumping and control. (water or glycol based)
- Description-Pipe-mounted UL 778 pumping unit with integrated intelligent controls for space-saving installation and superior energy performance. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations. Remote services through internet to enhance reliability and sustain optimal performance over life of pumps.
- Materials(MOC)-Ductile iron e-coated casing, Stainless steel impeller, Sintered silicon carbide mechanical seal
- Configuration-On-board Intelligent Variable Speed controls with Sensorless control. Split-coupling design and outside balanced or inside single spring mechanical seal. Controls enclosure UL type 12 or UL type 4X for outdoor applications. 0.33-50hp range standard with DEPM motors that reduce losses by more than 20% over NEMA Premium efficiency. Network capable for remote performance management services.
- Performance range-25 to 25,000 USgpm (1.5 to 1500 L/s) flow; 10 to 300 ft (3 to 90 m) head (composite curves available)
- Temperature-300oF (150oC)
- Power Range-0.33 hp to 1250 hp (0.25 kW to 900 kW)
- Size-1″ to 20″ (25 mm to 500 mm)
181
People watching this product now!
Description
Benefits & Features
Lowest installed cost
- Vertical In-line design eliminates the need for inertia bases, housekeeping pads, and flex connectors and reduces piping requirements.
- Integrated intelligent controls eliminate separate mounting of variable frequency drive (VFD) as well as procurement, installation (incl. wiring), calibration and upkeep of differential pressure sensor.
- Vertical motor positioning requires up to 60% less floor space compared to other pump configurations.
- Expertly staggered product line for perfect pump match-up and selection especially in retrofit situations.
- Superior energy performance qualifies for significant cost recovery under utility and government rebate programs.
- Design Envelope selections frequently recommend a smaller motor and/or pump which reduces installed cost.
Lowest operating cost
- Integrated intelligent controls – combined with perfect component match-up and tuning – for up to 75% in energy savings over traditional constant speed and variable frequency operated pump installations.
- Split-coupling design for easy seal service without removal of pump or motor.
Lowest environmental cost
- 75% decrease in energy consumption reduces operational greenhouse gas emissions at equal ratio.
- Elimination of inertia bases, housekeeping pads, flex connectors and superfluous piping avoids all procurement related environmental impacts. (material, energy, carbon)
- Equipment downsizing mitigates environmental impacts associated with procuring unnecessarily large equipment.
- Integrated design packs and ships more economically for less packaging waste compared to loose component shipping and assembly.
Lowest project and operating risk
- Integrated intelligent controls for fast and easy commissioning as well as reduced radio frequency interference/ improved electromagnetic compatibility.
- Optional performance management for early warnings, online trending and analysis, and reports and summaries.
- Optional sediment filters or separators for extended seal life in contaminated systems.
- Single-source responsibility for optimum design and field support.
- Independent operation through embedded Sensorless control or in conjunction with a building automation system (BAS)
- ETL Listed – conforms to UL STD 778
- Certified to CSA STD C22.2 NO.108